Summary

PRFS201707945
Fire Suppression System
Finaled
PHD PROPERTIES LLC
New
Design and install a new fire sprinkler system in a new apartment building.
08/25/2017
09/25/2017
09/10/2018
07/03/2018

Locations

Permits

Permit Number: PRFS201707945

Fire Suppression System
Finaled
09/25/2017
09/10/2018

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Progress Inspection Passed 10/16/2017
Corrections:


Miscellaneous/Other
Comment Only
10/16/2017
Inspection of progress of work. 4th floor appears close to being ready for rough-in inspection. Advised contractor to call for rough-in inspection as soon as work is ready and to install temp standpipe with FDC.

Fire Rough-in Inspection Partial Pass 10/27/2017
Corrections:


Miscellaneous/Other
Comment Only
10/27/2017
Ok to cover 3rd floor rooms only. End caps needed in room 300 and 301.

Fire Rough-in Inspection Partial Pass 10/27/2017
Corrections:


Comment Only
10/27/2017
4th floor rooms and corridor ok to cover. Temp Standpipe approved.

Fire Rough-in Inspection Failed 11/8/2017 (10:00 - 12:00) 11/8/2017 11/08/2017
Corrections:


Miscellaneous/Other
Outstanding
11/08/2017
City approved plans do not match installation. Advised contractor to resubmit plans and calcs.

Fire Rough-in Inspection Partial Pass 11/9/2017 (8:00 - 10:00) 11/9/2017 11/09/2017
Corrections:


Miscellaneous/Other
Resolved
11/09/2017
City approved plans do not match installation. Advised contractor to resubmit plans and calcs.

Miscellaneous/Other
Comment Only
11/09/2017
Rough in approved for floors 2 and 1. Sprinkler Contractor added pipe as needed per plan and will submit final as built drawing upon completion of project.

Fire Rough-in Inspection Failed 11/14/2017 (10:00 - 12:00) 11/14/2017 11/14/2017
Corrections:


Heads obstructed
Carried Forward
11/14/2017
Heads obstructed. Soffits create obstructions to sidewall sprinkler heads and need to be protected as such.

Fire Rough-in Inspection Partial Pass 11/16/2017 (10:00 - 12:00) 11/16/2017 11/16/2017
Corrections:


Heads obstructed
Resolved
11/16/2017
Heads obstructed. Soffits create obstructions to sidewall sprinkler heads and need to be protected as such.

Fire Rough-in Inspection Passed 11/29/2017 (8:00 - 10:00) 11/29/2017 12/01/2017
Fire Rough-in Inspection Partial Pass 12/11/2017 (8:00 - 10:00) 12/11/2017 12/12/2017
Fire Rough-in Inspection Partial Pass 2/16/2018 (8:00 - 10:00) 2/16/2018 02/16/2018
Corrections:


Miscellaneous/Other
Comment Only
02/16/2018
Trash chutes only.

Hydro Test Start Passed 2/20/2018 (10:00 - 12:00) 2/20/2018 02/20/2018
Hydro Test End Passed 2/20/2018 (12:30 - 2:30) 2/20/2018 02/20/2018
Fire Inspection Final Partial Pass 2/20/2018 (12:30 - 2:30) 2/20/2018 02/20/2018
Corrections:


Miscellaneous/Other
Outstanding
02/20/2018
Partial final approved. Test of flows and tampers approved. Need to raise sprinkler heads in Stair A and change out FDC to flush mount FDC style due to building obstructions.

Fire Inspection Final Passed 3/14/2018 (12:30 - 2:30) 3/14/2018 03/14/2018