Permit Application Status

PRFS201711515


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS201711515
Fire Suppression System
Finaled
THERMO KING CORPORATION
Alteration/Remodel
Relocate and provide new sprinklers, based on Fire Marshal requirements.
12/01/2017
12/05/2017
07/23/2018
01/24/2018

Locations

Permits

Permit Number: PRFS201711515

Fire Suppression System
Finaled
12/05/2017
07/23/2018

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Rough-in Inspection Failed 12/7/2017 (8:00 - 10:00) 12/7/2017 (AM) 12/07/2017
Corrections:


Miscellaneous/Other
Comment Only
12/07/2017
Receptionist unable to reach anyone to escort me to through the building and during inspection. Contractor needs to be on site for future inspections.

Fire Rough-in Inspection Partial Pass 12/11/2017 (12:30 - 2:30) 12/12/2017 (PM) 12/11/2017
Rough In inspection completed on 12/11/2017 at 13:00. Inspected Phase I - 2 conference rooms, storage room, photo room, patio entrance, hallway outside storage room and west office area. Ok to cover all but the hallway and west office area. Need 1 head added in hallway by patio entrance. Found several missing and broken hangers and painted heads above the west office ceiling area. Egg crate ceiling being installed in hallway outside storage/photo room. Need to verify whether or not coverage is required below the egg crate ceiling - thincell 3/8" white 2' by 2' styrene tile TC-22/30C7A002 sold by SLP Lighting. Need to verify whether or not sprinkler protection is needed above the ceiling (plenum space). Sprinkler coverage is being provide below the grid ceiling. lmccarthy 12/11/2017 4:05 PM
Corrections:


Miscellaneous/Other
Outstanding
12/22/2017
Rough In inspection completed on 12/11/2017 at 13:00. Inspected Phase I - 2 conference rooms, storage room, photo room, patio entrance, hallway outside storage room and west office area. Ok to cover all but the hallway and west office area. Need 1 head added in hallway by patio entrance. Found several missing and broken hangers and painted heads above the west office ceiling area. Egg crate ceiling being installed in hallway outside storage/photo room. Need to verify whether or not coverage is required below the egg crate ceiling - thincell 3/8" white 2' by 2' styrene tile TC-22/30C7A002 sold by SLP Lighting. Need to verify whether or not sprinkler protection is needed above the ceiling (plenum space). Sprinkler coverage is being provide below the grid ceiling. lmccarthy 12/11/2017 4:05 PM

Fire Inspection Final Partial Pass 12/22/2017 (8:00 - 10:00) 12/22/2017 12/22/2017
Corrections:


Miscellaneous/Other
Comment Only
12/22/2017
Partial final approved for ACT ceiling areas only.

Fire Rough-in Inspection VOID 01/17/2018
Fire Inspection Final Failed 1/18/2018 (12:30 - 2:30) 1/18/2018 (PM) 01/18/2018
Corrections:


Miscellaneous/Other
Outstanding
01/18/2018
Contractor to provide information on open-grid ceiling prior to final.

Fire Inspection Final Passed 1/24/2018 (10:00 - 12:00) 1/24/2018 01/24/2018