PRFS201800188
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Rough-in Inspection | Partial Pass | 3/14/2018 (10:00 - 12:00) | 3/14/2018 | 03/14/2018 |
Corrections:
Miscellaneous/Other
Comment Only
03/14/2018
Partial Rough In Approved for the following areas:
South elevator lobby
Market area
Public and Pool restrooms.
Also, advised sprinkler and general contractor of the following;
Replace all painted and/or corroded sprinkler heads as needed. Found several throughout the 1st floor.
Sprinkler protection needed for Air Handling room
Sprinkler Protection needed for new Beverage Stations.
Need to verity sprinkler protection in exsisting horizontal grease duct and reinstall/replace system and heads as needed.
|
||||
Fire Rough-in Inspection | Partial Pass | 4/6/2018 (8:00 - 10:00) | 4/6/2018 | 04/06/2018 |
Corrections:
Miscellaneous/Other
Comment Only
04/06/2018
Rough in approved for Willow and Palm meeting rooms.
|
||||
Fire Rough-in Inspection | Partial Pass | 6/1/2018 (10:00 - 12:00) | 6/1/2018 | 06/01/2018 |
Corrections:
Miscellaneous/Other
Comment Only
06/01/2018
Ok to cover hard lid near new hood. 6 heads.
|
||||
Fire Inspection Final | Passed | 6/26/2018 (12:30 - 2:30) | 6/26/2018 | 06/26/2018 |