PRFS201800822
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Rough-in Inspection | Partial Pass | 2/14/2018 (10:00 - 12:00) | 2/14/2018 | 02/14/2018 |
Hard lids only. | ||||
Corrections:
Miscellaneous/Other
Outstanding
02/14/2018
Ok to cover hard lids only. New walls have created obstructions that require alterations and another rough in inspection.
|
||||
Miscellaneous/Other
Outstanding
02/14/2018
Ductwork creates an obstruction greater than 4x4 that will require added coverage.
|
||||
Miscellaneous/Other
Outstanding
02/14/2018
One head buried in new wall sheet rock. Move head per listing.
|
||||
Fire Rough-in Inspection | Partial Pass | 02/14/2018 | ||
Corrections:
Miscellaneous/Other
Outstanding
02/14/2018
New walls have created obstructions that must be addressed. Ductwork greater than 4x4 will require coverage. Ensure heads that are too close to new walls are relocated per their listing. OK to cover hard lids only. Call for reinspection for other areas.
|
||||
Fire Rough-in Inspection | Partial Pass | 3/8/2018 (12:30 - 2:30) | 3/8/2018 | 03/08/2018 |
Ok to cover grid. | ||||
Fire Rough-in Inspection | Passed | 03/16/2018 | ||
Fire Inspection Final | Passed | 3/16/2018 (10:00 - 12:00) | 3/16/2018 | 03/16/2018 |