Summary

PRFS201800822
Fire Suppression System
Finaled
KRAUS-ANDERSON INC
Other
Add new pendent heads in new ceilings, add upright sprinklers where needed for new wall layout.
01/29/2018
02/13/2018
09/12/2018
03/16/2018

Locations

Permits

Permit Number: PRFS201800822

Fire Suppression System
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Rough-in Inspection Partial Pass 2/14/2018 (10:00 - 12:00) 2/14/2018 02/14/2018
Miscellaneous/Other
Outstanding
02/14/2018
Ok to cover hard lids only. New walls have created obstructions that require alterations and another rough in inspection.

Miscellaneous/Other
Outstanding
02/14/2018
Ductwork creates an obstruction greater than 4x4 that will require added coverage.

Miscellaneous/Other
Outstanding
02/14/2018
One head buried in new wall sheet rock. Move head per listing.

Fire Rough-in Inspection Partial Pass 02/14/2018
Miscellaneous/Other
Outstanding
02/14/2018
New walls have created obstructions that must be addressed. Ductwork greater than 4x4 will require coverage. Ensure heads that are too close to new walls are relocated per their listing. OK to cover hard lids only. Call for reinspection for other areas.

Fire Rough-in Inspection Partial Pass 3/8/2018 (12:30 - 2:30) 3/8/2018 03/08/2018
Fire Rough-in Inspection Passed 03/16/2018
Fire Inspection Final Passed 3/16/2018 (10:00 - 12:00) 3/16/2018 03/16/2018