PRFS201801528
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Rough-in Inspection | Passed | 4/16/2018 (8:00 - 10:00) | 4/16/2018 | 04/16/2018 |
Corrections:
Miscellaneous/Other
Resolved
04/16/2018
|
||||
Fire Inspection Final | Passed | 05/04/2018 | ||
Fire Rough-in Inspection | Passed | 05/04/2018 | ||
Fire Rough-in Inspection | Passed | 05/04/2018 | ||
Corrections:
Miscellaneous/Other
Outstanding
04/16/2018
Following additions/corrections need to be made and tested:
Add notification appliances as needed. Found several areas such as restrooms and stock rooms that were lacking notification appliances.
All non life safety audio (i.e music speakers) shall shut off upon activation of fire alarms.
Remove all old, non functioning fire alarm devices that were part of the old fire alarm system. Found an old ,non functioning fire alarm annunciation panel in the main office.
|