PRFS201810979
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Fire Inspection Final | Failed | 11/9/2018 (8:00 - 10:00) | 11/9/2018 (AM) | 11/09/2018 |
Corrections:
Miscellaneous/Other
Carried Forward
11/09/2018
No water flow with valve open, tamper and activation of system did not shut down power and gas, gas did not stay off with activation, copper plugs must be steel in hood, exhaust did not activate when switch was in the off position and system tripped, unable to verify if make up air shuts down upon activation of system, k-class fire extinguisher to be moved to near exit of the kitchen as it is too close to the hood. 10 pound ABC fire extinguisher to be added to space.
|
||||
Fire Inspection Final | Passed | 11/15/2018 (8:00 - 10:00) | 11/15/2018 (AM) | 11/15/2018 |
Corrections:
Miscellaneous/Other
Outstanding
11/09/2018
No water flow with valve open, tamper and activation of system did not shut down power and gas, gas did not stay off with activation, copper plugs must be steel in hood, exhaust did not activate when switch was in the off position and system tripped, unable to verify if make up air shuts down upon activation of system, k-class fire extinguisher to be moved to near exit of the kitchen as it is too close to the hood. 10 pound ABC fire extinguisher to be added to space.
|