PRFS201813434
Fire Suppression System
Finaled
OXBORO BLOOMINGTON RETAIL CENTER LLC
Alteration/Remodel
Change 25 pendent sprinkler heads to new upright sprinkler heads, add 2 additional upright sprinkler heads, and move 8 existing pendent sprinkler heads.
10/25/2018
11/01/2018
06/16/2019
12/18/2018

Locations

Permits

Permit Number: PRFS201813434

Fire Suppression System
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Rough-in Inspection Passed w/ Conditions 12/13/2018 (10:00 - 12:00) 12/13/2018 (AM) 12/13/2018
Corrections:


Miscellaneous/Other
Resolved
12/18/2018
Hard lids and ACT areas approved. Found several upright heads with paint over spray on them. Inspect and replace painted heads as needed. Additional sprinkler protection needed above mechanical and other rooms along the north wall.

Fire Inspection Final Passed 12/18/2018 (12:30 - 2:30) 12/18/2018 (PM) 12/18/2018