Summary

PRFS202012706
Fire Suppression System
Expired
THERMO KING CORPORATION
Other
Extend existing system to protect the newly remodeled office area that was previously not sprinklered. Add/relocate heads from existing system in office remodel in the basement level.
10/15/2020
11/05/2020
07/28/2021

Locations

Permits

Permit Number: PRFS202012706

Fire Suppression System
Expired
11/05/2020
07/28/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Inspection Final Pending
Fire Rough-in Inspection Not Ready 11/23/2020 (8:00 - 10:00) 11/23/2020 (AM) 11/23/2020
Fire Rough-in Inspection Partial Pass 12/1/2020 (8:00 - 10:00) 12/1/2020 (AM) 12/01/2020
Corrections:


Miscellaneous/Other
Comment Only
12/01/2020
Partial rough in approved for bulk pipe. Still need to inspect drops.

Hydro Test Start Passed 1/29/2021 (8:00 - 10:00) 1/29/2021 (AM) 01/29/2021
Fire Rough-in Inspection Passed w/ Conditions 1/29/2021 (8:00 - 10:00) 1/29/2021 (AM) 01/29/2021
Corrections:


Missing pipe hangers.
Comment Only
01/29/2021
Missing pipe hangers. Reattach pipe hanger around duct work and ventilation unit as needed.

Hydro Test End Passed 1/29/2021 (10:00 - 12:00) 1/29/2021 (AM) 01/29/2021
Corrections:


Miscellaneous/Other
Comment Only
01/29/2021
Hydro of new system, east half of office areas on all floors, and isolated from original fire sprinkler system. Passed 200 psi.