Permit Application Status

PRFS202300768


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRFS202300768
Fire Suppression System
Finaled
GKII NORTHLAND CENTER LLC
Alteration/Repair/Replace
Add new quick response heads to ceilings for remodel. Add preaction system to the server room.
01/25/2023
02/06/2023
08/11/2024
02/13/2024

Locations

Permits

Permit Number: PRFS202300768

Fire Suppression System
Finaled
02/06/2023
08/11/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Fire Rough-in Inspection Partial Pass 3/3/2023 (8:00 - 10:00) 3/3/2023 (AM) 03/03/2023
Ok to cover hard lid
Fire Rough-in Inspection Partial Pass 4/12/2023 (7:00 - 8:00) 4/12/2023 (AM) 04/12/2023
Portion of center area and south wing.
24-hr Air Test Start Passed 4/12/2023 (7:00 - 8:00) 4/12/2023 (AM) 04/12/2023
39 psi
24-hr Air Test End Passed 4/13/2023 (7:00 - 8:00) 4/13/2023 (AM) 04/13/2023
Lost about 1.5 psi
Fire Rough-in Inspection Partial Pass 4/21/2023 (10:00 - 12:00) 4/21/2023 (AM) 04/21/2023
North area and partial west.
Acceptance Test Inspection Passed 05/09/2023
Fire Inspection Final Passed 05/09/2023
Fire Rough-in Inspection Passed 5/9/2023 (10:00 - 12:00) 5/9/2023 (AM) 05/09/2023