PRFS202309730
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Fire Rough-in Inspection | Pending | |||
| Fire Inspection Final | Pending | |||
| Fire Rough-in Inspection | Partial Pass | 1/2/2024 (10:00 - 12:00) | 1/2/2024 (AM) | 01/04/2024 |
| Hard lid areas approved to be covered. | ||||
| Hydro Test End | Passed | 2/15/2024 | 2/15/2024 | 02/15/2024 |
| 200 psi | ||||
| Hydro Test Start | Passed | 2/15/2024 | 2/15/2024 | 02/15/2024 |
| 200 psi | ||||
| Hydro Test Start | Partial Pass | 2/15/2024 | 02/15/2024 | |
| Hydro for north end, showroom northeast quadrant. Starting psi 202. | ||||
| Hydro Test End | Partial Pass | 2/15/2024 | 02/15/2024 | |
| Ending psi 200 | ||||
| Fire Rough-in Inspection | Partial Pass | 3/6/2024 | 3/6/2024 | 03/06/2024 |
| Fire Rough-in Inspection | Partial Pass | 11/6/2024 (7:00 - 8:00) | 11/6/2024 (AM) | 11/06/2024 |
| Hallway off of maintenance shop and adjacent rooms approved. | ||||
| Fire Rough-in Inspection | Partial Pass | 12/16/2024 (8:00 - 10:00) | 12/16/2024 (AM) | 12/16/2024 |
| Shall add a sprinkler head to protect under the mezzanine stairs, remove old hanger brackets on the pipe west of the mezzanine. | ||||
| Fire Inspection Final | Not Ready | 12/16/2024 (8:00 - 10:00) | 12/16/2024 (AM) | 12/16/2024 |