PRFS202502941
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Fire Inspection Final | Pending | |||
| Fire Rough-in Inspection | Passed | 12/5/2025 (12:30 - 2:30) | 12/5/2025 (PM) | 12/05/2025 |
| Wet system | ||||
| 24-hr Air Test Start | Passed | 12/5/2025 (12:30 - 2:30) | 12/5/2025 (PM) | 12/05/2025 |
| for the dry test Starting psi 40 13:21 | ||||
| 24-hr Air Test End | Passed | 12/5/2025 (12:30 - 2:30) | 12/5/2025 (PM) | 12/08/2025 |
| Ending psi 38.5psi (read 12/8 07:38) | ||||
| Fire Inspection Final | Partial Pass | 12/5/2025 (12:30 - 2:30) | 12/5/2025 (PM) | 12/12/2025 |
| Wet system Needs to add tampers and monitoring to the OS&Y valves | ||||