PRMH201700780
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Mechanical Rough-in Inspection | Partial Pass | 4/13/2017 (10:00 - 12:00) | 4/13/2017 | 04/17/2017 |
Corrections:
Miscellaneous/Other
Comment Only
04/17/2017
Large Duct holding 1" of wc
|
||||
Mechanical Rough-in Inspection | Failed | 4/18/2017 (2:30 - 3:30) | 4/18/2017 | 04/18/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
04/18/2017
Light test main hood at collar ok.
Air test. Small duct. Not holding air
|
||||
Mechanical Rough-in Inspection | Failed | 4/21/2017 (12:30 - 2:30) | 4/21/2017 (AM) | 04/21/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
04/21/2017
Light test main hood at collar ok.
Air test. Small duct. Not holding air
|
||||
Mechanical Rough-in Inspection | Passed | 4/24/2017 (12:30 - 2:30) | 4/24/2017 | 04/24/2017 |
Corrections:
Miscellaneous/Other
Outstanding
04/21/2017
Light test main hood at collar ok.
Air test. Small duct. Not holding air
|
||||
Miscellaneous/Other
Outstanding
04/24/2017
.91wc". For 20 minutes. On small grease duct
|
||||
Mechanical Rough-in Inspection | Passed | 4/27/2017 (8:00 - 10:00) | 4/27/2017 | 04/27/2017 |
Corrections:
Miscellaneous/Other
Comment Only
04/27/2017
Light test both small and main duct. OK
|
||||
Mechanical Final Inspection | Not Ready | 5/4/2017 (3:30 - 4:00) | 5/4/2017 | 05/09/2017 |
Mechanical Final Inspection | Not Ready | 5/9/2017 (2:30 - 3:30) | 5/9/2017 | 05/09/2017 |
Corrections:
Miscellaneous/Other
Comment Only
05/09/2017
No balancing as of today.
|
||||
Mechanical Final Inspection | Passed | 5/10/2017 (8:00 - 3:30) | 5/10/2017 | 05/10/2017 |
Mechanical Final Inspection | VOID | 10/12/2017 |