| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Mechanical Rough-in Inspection | Passed | 4/25/2017 (2:30 - 3:30) | 4/25/2017 | 04/25/2017 |
|
Corrections:
Miscellaneous/Other
Comment Only
04/25/2017
30# air test on roof for mua and for gas under hood both sides. Grease duct inspection. Ok
|
||||
| Mechanical Final Inspection | Partial Pass | 5/25/2017 (12:30 - 2:30) | 5/25/2017 | 05/26/2017 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/26/2017
Hood not capturing due to serving drop down curtain creating air turbulence. Side panels warranted. Dish machine not working could not test hood. Make up air ok. Hi, lo limits. Ok. Modulating burner ok. Damper and air flow ok.
Ok to set up and cook if fire is ok
|
||||
| Mechanical Final Inspection | Passed | 9/12/2017 (8:00 - 10:00) | 9/12/2017 | 09/12/2017 |