Summary

PRMH201704392
Mechanical/HVAC
Finaled
;
MOAC LAND HOLDINGS LLC
Alteration/Remodel
1 RTU, 2 roof mounted grease fans, ductwork from rooftop with external insulation, welded grease duct from hood to roof, grills, registers and diffusers as specified, high temp insulation from hoods.
05/31/2017
06/08/2017
05/23/2020
10/02/2017

Locations

Permits

Permit Number: PRMH201704392

Mechanical
Finaled
06/08/2017
05/23/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Partial Pass 7/27/2017 (2:30 - 3:30) 7/27/2017 07/27/2017
Corrections:


Miscellaneous/Other
Comment Only
07/27/2017
Back grease ductwork 1" press. Ok. Front grease duct. Dropping pressure.

Mechanical Rough-in Inspection Passed 7/31/2017 (8:00 - 10:00) 7/31/2017 07/31/2017
Corrections:


Miscellaneous/Other
Comment Only
07/31/2017
Air test both grease ducts. 1.3"wc

Mechanical Rough-in Inspection Partial Pass 8/7/2017 (8:00 - 10:00) 8/7/2017 08/07/2017
Corrections:


Miscellaneous/Other
Comment Only
08/07/2017
Ok to wrap greaseduct

Mechanical Rough-in Inspection Passed 9/1/2017 09/01/2017
Corrections:


Outstanding
09/01/2017
Above ceiling RI OK. Wraps on grease ducts OK. Roof top fans and grease duct OK No leaks noted.

Mechanical Final Inspection Passed 10/2/2017 (7:00 - 8:00) 10/2/2017 10/02/2017