PRMH201707975
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Mechanical Rough-in Inspection | Partial Pass | 9/7/2017 (12:30 - 2:30) | 9/7/2017 | 09/07/2017 |
Corrections:
Miscellaneous/Other
Comment Only
09/07/2017
Ok to insulate round duct
|
||||
Mechanical Rough-in Inspection | Partial Pass | 9/21/2017 (8:00 - 10:00) | 9/21/2017 | 09/21/2017 |
Mechanical Rough-in Inspection | Passed | 10/26/2017 (8:00 - 10:00) | 10/26/2017 | 10/26/2017 |
Air-test on grease duct good need to add access doors ok to insulate duct in bathrooms and kitchen areajsoller 09/21/2017 4:18 PM | ||||
Corrections:
Miscellaneous/Other
Comment Only
10/26/2017
Above ceiling in bathrooms on east and west side okay could not totally view bathroom on West due to sheetrock on ceiling. Caulk being used to put heads into grease duct, contractor was told by Barry that that will not be allowed, use the proper flange
|
||||
Mechanical Rough-in Inspection | Partial Pass | 10/30/2017 (10:00 - 12:00) | 10/30/2017 | 10/30/2017 |
Mechanical Rough-in Inspection | Partial Pass | 11/1/2017 (8:00 - 10:00) | 11/1/2017 | 11/02/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/02/2017
Light test of connection to main grease duct to hood ok
|
||||
Mechanical Rough-in Inspection | Partial Pass | 11/7/2017 (8:00 - 10:00) | 11/7/2017 | 11/07/2017 |
Mechanical Rough-in Inspection | Partial Pass | 11/9/2017 (8:00 - 10:00) | 11/9/2017 | 11/09/2017 |
Mechanical Rough-in Inspection | Passed | 11/15/2017 (8:00 - 10:00) | 11/15/2017 | 11/15/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/15/2017
Grease duct Southside three hoods okay no light Lakes noted
|
||||
Mechanical Rough-in Inspection | Partial Pass | 11/29/2017 (8:00 - 10:00) | 11/29/2017 | 11/29/2017 |
Mechanical Rough-in Inspection | Passed | 1/10/2018 (10:00 - 12:00) | 1/10/2018 | 01/10/2018 |
Give additional 30 minutes. | ||||
Corrections:
Miscellaneous/Other
Comment Only
01/10/2018
Make-up air startup okay high limit low limit airflow.
|
||||
Miscellaneous/Other
Comment Only
01/10/2018
High limit low limit airflow all good
|
||||
Mechanical Final Inspection | Partial Pass | 3/26/2018 (10:00 - 12:00) | 3/26/2018 | 03/26/2018 |
Mechanical Final Inspection | Passed | 05/08/2018 |