Permit Application Status

PRMH201803503


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMH201803503
Mechanical/HVAC
Expired
BLMGTN SCHOOL DIST #271
Repair/Replace
install new chilled water pipe, hot water pipe 2 condensing boilers, 2 RTU, stearm to converter, and duct work.
04/20/2018
05/08/2018
03/09/2019

Locations

Permits

Permit Number: PRMH201803503

Mechanical
Expired
05/08/2018
03/09/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Final Inspection Pending
Mechanical Rough-in Inspection Partial Pass 7/10/2018 (12:30 - 2:30) 7/10/2018 (PM) 07/11/2018
Mechanical Rough-in Inspection Partial Pass 07/11/2018
Mechanical Rough-in Inspection Partial Pass 7/16/2018 (12:30 - 2:30) 7/16/2018 07/16/2018
Corrections:


Miscellaneous/Other
Comment Only
07/16/2018
All gas piping to new boilers on roof and venting from boilers ok

Mechanical Rough-in Inspection Passed 7/27/2018 (10:00 - 12:00) 7/27/2018 07/27/2018
Corrections:


Miscellaneous/Other
Comment Only
07/27/2018
All 6” chilled water hot water to cafe all holding 90psi

Mechanical Rough-in Inspection Partial Pass 8/1/2018 (Afternoon) 8/1/2018 08/02/2018
Corrections:


Miscellaneous/Other
Comment Only
08/02/2018
90 psi on all cw and hw piping

Mechanical Rough-in Inspection Partial Pass 8/6/2018 (10:00 - 12:00) 8/6/2018 (AM) 08/06/2018
Mechanical Rough-in Inspection Partial Pass 8/14/2018 (10:00 - 12:00) 8/14/2018 08/14/2018
Corrections:


Miscellaneous/Other
Comment Only
08/14/2018
Pressure test on hot water piping

Mechanical Rough-in Inspection Partial Pass 8/16/2018 (Morning) 8/16/2018 08/16/2018
Corrections:


Miscellaneous/Other
Outstanding
08/16/2018
Chilled water air test 90 psi see paper work for area

Mechanical Rough-in Inspection Partial Pass 8/20/2018 (8:00 - 10:00) 8/20/2018 08/21/2018
Corrections:


Miscellaneous/Other
Comment Only
08/21/2018
Duct serving the gym area and new return duct need grills installed and balanced

Mechanical Rough-in Inspection Passed 8/22/2018 (10:00 - 12:00) 8/22/2018 08/22/2018
Corrections:


Miscellaneous/Other
Comment Only
08/22/2018
See paperwork

Mechanical Rough-in Inspection Passed 8/23/2018 (10:00 - 12:00) 8/23/2018 08/23/2018
Corrections:


Miscellaneous/Other
Comment Only
08/23/2018
All air test are completed and performed to as on the specs

Mechanical Final Inspection Partial Pass 8/30/2018 (12:30 - 2:30) 8/30/2018 09/04/2018
Corrections:


Miscellaneous/Other
Comment Only
09/04/2018
All duct and piping complete need commissioning report

Mechanical Final Inspection Partial Pass 09/10/2018