Permit Application Status

PRMH201808979


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMH201808979
Mechanical/HVAC
Closed
CYPRESS SEMICONDUCTOR INC
Alteration/Remodel
New HVAC for clean room. Daikin, 818,827 BTU's, 10,000 CFM, Model #OAH024GDGM, Hydronic fuel.
08/10/2018
08/24/2018
02/20/2019
01/08/2019

Locations

Permits

Permit Number: PRMH201808979

Mechanical
Closed
08/24/2018
02/20/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
01/09/2019
Need balance report

Mechanical Rough-in Inspection Partial Pass 11/6/2018 (8:00 - 10:00) 11/6/2018 (AM) 11/06/2018
Corrections:


Miscellaneous/Other
Comment Only
11/06/2018
Pressure test on first cooling lines

Mechanical Rough-in Inspection Partial Pass 11/8/2018 (8:00 - 10:00) 11/8/2018 (AM) 11/09/2018
Corrections:


Miscellaneous/Other
Comment Only
11/08/2018
Pressure test on piping ok holding 100 psi ok to insulate

Mechanical Rough-in Inspection Passed 11/20/2018 (8:00 - 10:00) 11/20/2018 (AM) 11/20/2018
Corrections:


Miscellaneous/Other
Comment Only
11/20/2018
Pressure test gas lines to units from boiler room holding 25 psi

Mechanical Final Inspection Partial Pass 12/19/2018 (8:00 - 10:00) 12/19/2018 (AM) 01/09/2019
Corrections:


Miscellaneous/Other
Carried Forward
01/09/2019
Need balance report