Summary

PRMH201809937
Mechanical/HVAC
Expired
101 AMERICAN BLVD W LLC
Alteration/Repair/Replace
Rooftop Units, Exhaust Fans, Electric Unit Heaters, Ductwork, Dampers
08/28/2018
07/12/2019
06/03/2020

Locations

Permits

Permit Number: PRMH201809937

Mechanical
Expired
07/12/2019
06/03/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Partial Pass 10/11/2019 (8:00 - 10:00) 10/11/2019 (AM) 10/11/2019
Mechanical Rough-in Inspection Partial Pass 10/15/2019 (8:00 - 10:00) 10/15/2019 (AM) 10/15/2019
Mechanical Rough-in Inspection Partial Pass 10/18/2019 (10:00 - 12:00) 10/18/2019 (AM) 10/18/2019
Corrections:


Miscellaneous/Other
Comment Only
10/18/2019
Gas pressure test ok

Mechanical Rough-in Inspection Failed 10/22/2019 (10:00 - 12:00) 10/22/2019 (AM) 10/22/2019
Mechanical Rough-in Inspection Failed 10/25/2019 (10:00 - 12:00) 10/25/2019 (AM) 10/25/2019
Mechanical Rough-in Inspection Passed 10/29/2019 (10:00 - 12:00) 10/29/2019 (AM) 10/29/2019
Mechanical Rough-in Inspection Partial Pass 11/6/2019 (12:30 - 2:30) 11/6/2019 (PM) 11/06/2019
Corrections:


Miscellaneous/Other
Carried Forward
11/08/2019
Fire angles installed at each job location at floor to be addressed. The angles that are in place do not cover the floor opening.Fire caulk at corners where angles meet, and any openings of electrical work angles are cut out.

Miscellaneous/Other
Comment Only
11/06/2019
Fuse-a-ble dampers at each floor duct location approved. See “outstanding” comment for correction.

Mechanical Rough-in Inspection Failed 11/8/2019 (10:00 - 12:00) 11/8/2019 (AM) 11/08/2019
Mechanical Final Inspection Partial Pass 11/13/2019 (8:00 - 10:00) 11/13/2019 (AM) 11/13/2019
Corrections:


Miscellaneous/Other
Carried Forward
11/13/2019
Fire angles installed at each job location at floor to be addressed. The angles that are in place do not cover the floor opening.Fire caulk at corners where angles meet, and any openings of electrical work angles are cut out.

Mechanical Final Inspection Passed 12/2/2019 (10:00 - 12:00) 12/2/2019 (AM) 12/02/2019
Mechanical Final Inspection Passed 12/6/2019 (10:00 - 12:00) 12/6/2019 (AM) 12/06/2019
Corrections:


Miscellaneous/Other
Outstanding
11/13/2019
Fire angles installed at each job location at floor to be addressed. The angles that are in place do not cover the floor opening.Fire caulk at corners where angles meet, and any openings of electrical work angles are cut out.