Summary

PRMH202101952
Mechanical/HVAC
Expired
OSBORNE PROPERTIES
Alteration/Repair/Replace
Tenant HVAC work for Dunkin to include duct work, kitchen hoods (type 2), restroom exhaust, GRDs and balancing.
02/26/2021
03/03/2021
12/22/2021

Locations

Permits

Permit Number: PRMH202101952

Mechanical
Expired
03/03/2021
12/22/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Pending
Mechanical Final Inspection Pending
Mechanical Rough-in Inspection Partial Pass 3/31/2021 (10:00 - 12:00) 3/31/2021 (AM) 03/31/2021
Corrections:


Miscellaneous/Other
Comment Only
03/31/2021
Ok to wrap duct

Mechanical Rough-in Inspection Partial Pass 4/14/2021 (2:30 - 3:30) 4/14/2021 (PM) 04/14/2021
Mechanical Final Inspection Failed 6/2/2021 (10:00 - 12:00) 6/2/2021 (AM) 06/02/2021
Corrections:


Miscellaneous/Other
Comment Only
06/02/2021
Appliances not installed need to test hoods need perforated diffusers in kitchen

Mechanical Rough-in Inspection Failed 6/2/2021 (10:00 - 12:00) 6/2/2021 (AM) 06/02/2021
Mechanical Final Inspection Failed 6/9/2021 (2:30 - 3:30) 6/9/2021 (PM) 06/09/2021
Corrections:


Miscellaneous/Other
Comment Only
06/09/2021
Need to see fans interlocked with rtus and balance report

Mechanical Final Inspection Issue TCO 6/25/2021 (8:00 - 10:00) 6/25/2021 (AM) 06/25/2021
Temp occupancy - A. Manual test for interior warm air hood, temp activated inter connected to roof top supply. Supply Diffusers replaced with non directional type. Pass. B. Roof top mechanical unit for smoke detection - ? need Jesse Soller to confirm. C. 30 day temp. STORE ONLY TRAINING AT THIS TIME.