Permit Application Status

PRMH202113788


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMH202113788
Mechanical/HVAC
Finaled
AEON VP BLOOMINGTON LLC
Alteration/Repair/Replace
“Connect hot water wall heaters”
10/15/2021
10/18/2021
04/30/2022
11/01/2021

Locations

Permits

Permit Number: PRMH202113788

Mechanical
Finaled
10/18/2021
04/30/2022

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Final Inspection Passed w/ Conditions 11/1/2021 (2:30 - 3:30) 11/1/2021 (PM) 11/01/2021
Corrections:


Miscellaneous/Other
Comment Only
11/01/2021
Air tests holding at 80 psi… approved

Miscellaneous/Other
Comment Only
11/01/2021
1) Insulation needs to be zip tied or taped due to adhesive not holding, and elbows should be wrapped as well. 2) Access panels needed at shutoff valves buried in the built out wall of buildings 1900 & 1930.