Summary

PRMH202207334
Mechanical/HVAC
Expired
CITY OF BLOOMINGTON
Other
New HVAC for new Fire Station.
06/22/2022
08/24/2022
12/12/2023

Locations

Permits

Permit Number: PRMH202207334

Mechanical
Expired
08/24/2022
12/12/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
06/15/2023
Balance report needed for final of this permit.

Mechanical Rough-in Inspection Passed 1/31/2023 (12:30 - 2:30) 1/31/2023 (PM) 01/31/2023
Mechanical Rough-in Inspection Partial Pass 2/27/2023 (12:30 - 2:30) 2/27/2023 (PM) 02/27/2023
Mechanical Rough-in Inspection Partial Pass 3/9/2023 (8:00 - 10:00) 3/9/2023 (AM) 03/09/2023
Mechanical Rough-in Inspection Failed 4/12/2023 (12:30 - 2:30) 4/12/2023 (PM) 04/13/2023
Corrections:


Miscellaneous/Other
Comment Only
04/13/2023
Need a fresh air brought into 2nd floor laundry for gas dryer

Mechanical Rough-in Inspection Partial Pass 4/20/2023 (12:30 - 2:30) 4/20/2023 (PM) 04/20/2023
Mechanical Rough-in Inspection Partial Pass 4/26/2023 (8:00 - 10:00) 4/26/2023 (AM) 04/26/2023
Mechanical Final Inspection Partial Pass 6/15/2023 (12:30 - 2:30) 6/15/2023 (PM) 06/15/2023
Corrections:


Miscellaneous/Other
Comment Only
06/15/2023
Tested all dampers & general alarm. No2 & CO2 detection system tested. Hood fan tested and is to be tied into the VAV for make up air. Dryer venting approved. All systems tested were functional... Balance report needed for final of this permit.

Miscellaneous/Other
Carried Forward
06/15/2023
Balance report needed for final of this permit.