Permit Application Status

PRMH202301598


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMH202301598
Mechanical/HVAC
Finaled
BLOOMINGTON QOZ VENTURES LLC
Other
Complete hvac system in new 242 unit building
02/21/2023
04/12/2023
06/01/2025

Locations

Permits

Permit Number: PRMH202301598

Mechanical
Finaled
04/12/2023
06/01/2025

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Partial Pass 1/31/2024 (2:30 - 3:30) 1/31/2024 (PM) 01/31/2024
Mechanical Rough-in Inspection Partial Pass 2/13/2024 (10:00 - 12:00) 2/13/2024 (AM) 02/13/2024
Mechanical Rough-in Inspection Partial Pass 2/20/2024 (10:00 - 12:00) 2/20/2024 (AM) 02/20/2024
Corrections:


Miscellaneous/Other
Comment Only
02/20/2024
6th floor soffits on south end

Mechanical Rough-in Inspection Partial Pass 2/27/2024 (8:00 - 10:00) 2/27/2024 (AM) 02/27/2024
Corrections:


Miscellaneous/Other
Comment Only
02/27/2024
Ducting at soffits on Area "B" of sixth floor... approved. Gas lines and rough in of 5th floor areas " A&B" ... approved

Mechanical Rough-in Inspection Partial Pass 3/5/2024 (8:00 - 10:00) 3/5/2024 (AM) 03/05/2024
Mechanical Rough-in Inspection Partial Pass 3/29/2024 (8:00 - 10:00) 03/06/2024
Corrections:


Miscellaneous/Other
Comment Only
03/06/2024
Viewed ducting in soffits of units on 6th floor area B... approved

Progress Inspection Partial Pass 03/08/2024
Corrections:


Miscellaneous/Other
Comment Only
03/08/2024
Ducting in soffits of units in area 6A approved, except for the far incomplete end two units... setup inspection of those two units when ready.

Progress Inspection Partial Pass 03/11/2024
Corrections:


Miscellaneous/Other
Comment Only
03/11/2024
Remaing units of ducting in soffits of floor 6, area A... approved

Mechanical Rough-in Inspection Partial Pass 3/12/2024 (8:00 - 10:00) 3/12/2024 (AM) 03/12/2024
Progress Inspection Partial Pass 03/18/2024
Corrections:


Miscellaneous/Other
Comment Only
03/18/2024
Ducting in soffits of floor 5 about 2/3 of area C. Inspection signoff on door cards where inspected and approved

Mechanical Rough-in Inspection Partial Pass 3/19/2024 (8:00 - 10:00) 3/19/2024 (AM) 03/19/2024
Progress Inspection Partial Pass 03/21/2024
Corrections:


Miscellaneous/Other
Comment Only
03/21/2024
7 units of soffit ducting on 5th floor area B... approved

Mechanical Rough-in Inspection Passed 3/26/2024 (8:00 - 10:00) 3/26/2024 (AM) 03/26/2024
Mechanical Rough-in Inspection Partial Pass 4/2/2024 (8:00 - 10:00) 4/2/2024 (AM) 04/01/2024
Mechanical Rough-in Inspection Partial Pass 3/29/2024 (8:00 - 10:00) 3/29/2024 (AM) 04/01/2024
Mechanical Rough-in Inspection Partial Pass 4/9/2024 (8:00 - 10:00) 4/9/2024 (AM) 04/09/2024
Mechanical Rough-in Inspection Passed 4/12/2024 (8:00 - 10:00) 4/12/2024 (AM) 04/12/2024
Corrections:


Miscellaneous/Other
Comment Only
04/12/2024
Soffit ducting in units 421-431... approved

Mechanical Rough-in Inspection Not Ready 4/16/2024 (8:00 - 10:00) 4/16/2024 (AM) 04/16/2024
Corrections:


Miscellaneous/Other
Comment Only
04/16/2024
Inspection canceled by contractor, not ready.

Mechanical Rough-in Inspection Partial Pass 4/18/2024 (10:00 - 12:00) 4/18/2024 (AM) 04/18/2024
Mechanical Rough-in Inspection Partial Pass 4/23/2024 (8:00 - 10:00) 4/23/2024 (AM) 04/23/2024
Mechanical Rough-in Inspection Partial Pass 4/26/2024 (8:00 - 10:00) 4/26/2024 (AM) 04/26/2024
Mechanical Rough-in Inspection Partial Pass 4/30/2024 (8:00 - 10:00) 4/30/2024 (AM) 05/01/2024
Mechanical Rough-in Inspection Passed 05/02/2024
Corrections:


Miscellaneous/Other
Comment Only
05/02/2024
Ducting in soffits of units on 3rd floor, area B... approved

Progress Inspection Partial Pass 9/11/2024 (10:00 - 12:00) 9/11/2024 (AM) 09/11/2024
Progress Inspection Passed 09/24/2024
Corrections:


Miscellaneous/Other
Comment Only
09/24/2024
Testing of all smoke fire dampers in building with fire alarm system. Approved.

Mechanical Rough-in Inspection Partial Pass 10/3/2024 (10:00 - 12:00) 10/3/2024 (AM) 10/07/2024
Corrections:


Miscellaneous/Other
Carried Forward
10/07/2024
30 psi main gas line test passed

Mechanical Final Inspection Partial Pass 10/30/2024 (10:00 - 12:00) 10/30/2024 (AM) 10/30/2024
Final out the units
Mechanical Final Inspection Partial Pass 10/31/2024 (8:00 - 10:00) 10/31/2024 (AM) 11/06/2024
Corrections:


Miscellaneous/Other
Outstanding
11/06/2024
Dryer vent and gas htg equipment inspection-1st floor up htg equipment pass. Dryers pass except rm: 632.521,529,451,311 and 317. Exhaust fans could not be checked due to no power in units

Mechanical Final Inspection Partial Pass 10/31/2024 (10:00 - 12:00) 10/31/2024 (AM) 11/06/2024
Mechanical Final Inspection Passed 12/2/2024 (10:00 - 12:00) 12/2/2024 (AM) 12/03/2024