Summary

PRMH202304457
Mechanical/HVAC
Finaled
8925 LYNDALE LLC
Alteration/Repair/Replace
Install 2 roof top units, Make up air unit, exhaust fans, unit heaters, ductwork.
05/03/2023
05/15/2023
03/04/2024
09/06/2023

Locations

Permits

Permit Number: PRMH202304457

Mechanical
Finaled
05/15/2023
03/04/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Partial Pass 6/12/2023 (8:00 - 10:00) 6/12/2023 (AM) 06/12/2023
Corrections:


Miscellaneous/Other
Comment Only
06/12/2023
Above ceiling inspection okay for front of space on west side and above bathrooms.

Mechanical Final Inspection Not Ready 8/28/2023 (10:00 - 12:00) 8/28/2023 (AM) 08/28/2023
Mechanical Rough-in Inspection Partial Pass 8/28/2023 (10:00 - 12:00) 8/28/2023 (AM) 08/28/2023
Corrections:


Miscellaneous/Other
Carried Forward
08/28/2023
Need to see no/co detectors calibrated correctly need paint booth supervisor start ups need paper work for typo Make up air water heater venting through plenum and a gas fitting in plenum needs to be fixed

Mechanical Rough-in Inspection Passed 9/1/2023 (10:00 - 12:00) 9/1/2023 (AM) 09/01/2023
Corrections:


Miscellaneous/Other
Outstanding
08/28/2023
Need to see no/co detectors calibrated correctly need paint booth supervisor start ups need paper work for typo Make up air water heater venting through plenum and a gas fitting in plenum needs to be fixed

Mechanical Final Inspection Failed 9/1/2023 (10:00 - 12:00) 9/1/2023 (AM) 09/01/2023
Corrections:


Miscellaneous/Other
Comment Only
09/01/2023
Need to test no and co detectors

Mechanical Final Inspection Passed 9/6/2023 (10:00 - 12:00) 9/6/2023 (AM) 09/06/2023