Permit Application Status

PRMH202408528


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMH202408528
Mechanical/HVAC
Finaled
THE KNOX LLC
Other
Complete hvac system in new 99 unit apartment
07/01/2024
07/16/2024
09/15/2025
03/19/2025

Locations

Permits

Permit Number: PRMH202408528

Mechanical
Finaled
07/16/2024
09/15/2025

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Partial Pass 10/3/2024 (10:00 - 12:00) 10/3/2024 (AM) 10/07/2024
Corrections:


Miscellaneous/Other
Carried Forward
10/07/2024
4th floor Mock up passed and 10 4th floor rooms passes

Mechanical Rough-in Inspection Partial Pass 10/8/2024 (2:30 - 3:30) 10/8/2024 (PM) 10/10/2024
Corrections:


Miscellaneous/Other
Carried Forward
10/10/2024
4th floor Mock up passed and 10 4th floor rooms passes. 10/7-4th floor phase 1 rough-in pass inspection

Mechanical Rough-in Inspection Partial Pass 10/15/2024 (10:00 - 12:00) 10/15/2024 (AM) 10/16/2024
Corrections:


Miscellaneous/Other
Carried Forward
10/16/2024
4th floor Mock up passed and 10 4th floor rooms passes. 10/7-4th floor phase 1 rough-in pass inspection

Miscellaneous/Other
Carried Forward
10/16/2024
10/15 4th floor phase 2 rough in passed

Mechanical Rough-in Inspection Partial Pass 10/18/2024 (8:00 - 10:00) 10/18/2024 (AM) 10/21/2024
Corrections:


Miscellaneous/Other
Outstanding
10/16/2024
4th floor Mock up passed and 10 4th floor rooms passes. 10/7-4th floor phase 1 rough-in pass inspection

Miscellaneous/Other
Outstanding
10/16/2024
10/15 4th floor phase 2 rough in passed

Miscellaneous/Other
Outstanding
10/21/2024
Soffit duct work inspection pass 10/17

Mechanical Rough-in Inspection Partial Pass 10/21/2024 (10:00 - 12:00) 10/21/2024 (AM) 10/23/2024
Corrections:


Miscellaneous/Other
Carried Forward
10/28/2024
3rd floor dryer and exhaust vents need more looking into and fire caulk not complete

Mechanical Rough-in Inspection Partial Pass 10/24/2024 (Morning) 10/24/2024 (AM) 10/30/2024
Corrections:


Miscellaneous/Other
Carried Forward
11/06/2024
10/24 3rd floor fire caulk passed and dryer/bath fan exhaust passed

Mechanical Rough-in Inspection Partial Pass 10/30/2024 (2:30 - 3:30) 10/30/2024 (PM) 11/06/2024
Corrections:


Miscellaneous/Other
Outstanding
10/28/2024
3rd floor dryer and exhaust vents need more looking into and fire caulk not complete 10/30 soffit duct pass and 3rd fire caulk pass

Mechanical Rough-in Inspection Partial Pass 11/7/2024 (10:00 - 12:00) 11/7/2024 (AM) 11/07/2024
Corrections:


Miscellaneous/Other
Outstanding
11/06/2024
10/24 3rd floor fire caulk passed and dryer/bath fan exhaust passed. 3rd floor soffit pass 11/7

Mechanical Rough-in Inspection Partial Pass 11/12/2024 (2:30 - 3:30) 11/12/2024 (PM) 11/13/2024
Corrections:


Miscellaneous/Other
Carried Forward
11/13/2024
11/12 3rd floor soffit inspection pass

Mechanical Rough-in Inspection Partial Pass 11/19/2024 (10:00 - 12:00) 11/19/2024 (AM) 11/19/2024
Corrections:


Miscellaneous/Other
Carried Forward
11/19/2024
11/12 3rd floor soffit inspection pass

Miscellaneous/Other
Carried Forward
11/19/2024
11/9-1st floor dryer and exhaust fire caulk inspection passed and pvc condensate pipe fire caulk passed

Mechanical Rough-in Inspection Partial Pass 11/22/2024 (8:00 - 10:00) 11/22/2024 (AM) 11/22/2024
Corrections:


Miscellaneous/Other
Carried Forward
11/22/2024
11/12 3rd floor soffit inspection pass

Miscellaneous/Other
Carried Forward
11/22/2024
11/9-1st floor dryer and exhaust fire caulk inspection passed and pvc condensate pipe fire caulk passed

Miscellaneous/Other
Carried Forward
11/22/2024
11/22 soffit inspection west 2nd floor passed

Mechanical Rough-in Inspection Partial Pass 12/2/2024 (8:00 - 10:00) 12/2/2024 (AM) 12/02/2024
Corrections:


Miscellaneous/Other
Carried Forward
12/10/2024
West 2nd floor soffit duct is good to go

Mechanical Rough-in Inspection Partial Pass 12/10/2024 (8:00 - 10:00) 12/10/2024 (AM) 12/10/2024
Corrections:


Miscellaneous/Other
Outstanding
11/22/2024
11/12 3rd floor soffit inspection pass

Miscellaneous/Other
Outstanding
11/22/2024
11/9-1st floor dryer and exhaust fire caulk inspection passed and pvc condensate pipe fire caulk passed

Miscellaneous/Other
Outstanding
11/22/2024
11/22 soffit inspection west 2nd floor passed and riser shaft rough in and garbage venting pass.

Miscellaneous/Other
Outstanding
12/10/2024
12/10 1st floor soffit inspection pass Riser shaft and garbage exhaust insulation pass.

Mechanical Rough-in Inspection Partial Pass 12/19/2024 (8:00 - 10:00) 12/19/2024 (AM) 12/19/2024
Corrections:


Miscellaneous/Other
Carried Forward
12/19/2024
West 2nd floor soffit duct is good to go

Miscellaneous/Other
Carried Forward
12/19/2024
12/19-1st floor west soffit inspection pass

Mechanical Rough-in Inspection Partial Pass 1/8/2025 (8:00 - 10:00) 1/8/2025 (AM) 01/08/2025
Corrections:


Miscellaneous/Other
Carried Forward
01/08/2025
West 2nd floor soffit duct is good to go

Miscellaneous/Other
Carried Forward
01/08/2025
12/19-1st floor west soffit inspection pass

Miscellaneous/Other
Carried Forward
01/08/2025
1/8- rough-in inspection of ductwork in common area 1st floor. 30 psi air test on gas piping in underground parking garage-pass. 50 psi air test on snowmelt piping-pass

Mechanical Final Inspection Partial Pass 2/27/2025 (10:00 - 12:00) 2/27/2025 (AM) 02/27/2025
Corrections:


Miscellaneous/Other
Carried Forward
02/27/2025
2/27 All apt units bath exhaust, heat pumps and dryer venting I could see are all pass, More inspections to come.

Mechanical Rough-in Inspection Passed 03/19/2025
Corrections:


Miscellaneous/Other
Outstanding
01/08/2025
West 2nd floor soffit duct is good to go

Miscellaneous/Other
Outstanding
01/08/2025
12/19-1st floor west soffit inspection pass

Miscellaneous/Other
Outstanding
01/08/2025
1/8- rough-in inspection of ductwork in common area 1st floor. 30 psi air test on gas piping in underground parking garage-pass. 50 psi air test on snowmelt piping-pass

Mechanical Final Inspection Passed 3/11/2025 (10:00 - 12:00) 3/11/2025 (AM) 03/19/2025
Corrections:


Miscellaneous/Other
Outstanding
02/27/2025
2/27 All apt units bath exhaust, heat pumps and dryer venting I could see are all pass, More inspections to come.

Miscellaneous/Other
Outstanding
03/11/2025
Underground parking CO detectors/fan test passed. Smoke fire damper test passed on hallways. Underground parking visual ok Except for hanger on west unit heater flue and relief discharge on snowmelt boiler. Balance reports coming. Very nice job