Summary

PRMH202500232
Mechanical/HVAC
Finaled
CITY OF BLOOMINGTON
Alteration/Repair/Replace
3-Floor and Refrigeration System
01/08/2025
03/12/2025
07/13/2026
01/14/2026

Locations

Permits

Permit Number: PRMH202500232

Mechanical
Finaled
03/12/2025
07/13/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Partial Pass 4/25/2025 (12:30 - 2:30) 4/25/2025 (PM) 04/25/2025
underground rough-in
Corrections:


Miscellaneous/Other
Carried Forward
04/25/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Mechanical Rough-in Inspection Partial Pass 5/6/2025 (10:00 - 12:00) 5/6/2025 (AM) 05/06/2025
Corrections:


Miscellaneous/Other
Carried Forward
05/06/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
05/06/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Mechanical Rough-in Inspection Partial Pass 5/14/2025 (8:00 - 10:00) 5/14/2025 (AM) 05/14/2025
Corrections:


Miscellaneous/Other
Carried Forward
05/14/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
05/14/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Carried Forward
05/14/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Mechanical Rough-in Inspection Partial Pass 5/19/2025 (10:00 - 12:00) 5/19/2025 (AM) 05/19/2025
Corrections:


Miscellaneous/Other
Carried Forward
05/19/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
05/19/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Carried Forward
05/19/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Miscellaneous/Other
Carried Forward
05/19/2025
5/10- Rink #1 3” piping, headers and tubing. 100 psi hydrostatic test pass.

Mechanical Final Inspection Partial Pass 6/2/2025 (8:00 - 10:00) 6/2/2025 (AM) 06/04/2025
Rink 1-final piping
Corrections:


Miscellaneous/Other
Carried Forward
06/04/2025
Ice Rink 1 air test on all piping, header and grid pass. Concrete pour on Tuesday

Mechanical Rough-in Inspection Partial Pass 6/11/2025 (10:00 - 12:00) 6/11/2025 (AM) 06/11/2025
Corrections:


Miscellaneous/Other
Carried Forward
06/11/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
06/11/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Carried Forward
06/11/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Miscellaneous/Other
Carried Forward
06/11/2025
5/10- Rink #1 3” piping, headers and tubing. 100 psi hydrostatic test pass.

Miscellaneous/Other
Carried Forward
06/11/2025
6/11- Rink 2 melt grid and mains test pass

Mechanical Rough-in Inspection Partial Pass 6/20/2025 (12:30 - 2:30) 6/20/2025 (PM) 06/20/2025
Corrections:


Miscellaneous/Other
Carried Forward
06/20/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
06/20/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Carried Forward
06/20/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Miscellaneous/Other
Carried Forward
06/20/2025
5/10- Rink #1 3” piping, headers and tubing. 100 psi hydrostatic test pass.

Miscellaneous/Other
Carried Forward
06/20/2025
6/11- Rink 2 melt grid and mains test pass

Miscellaneous/Other
Carried Forward
06/20/2025
6/20- Rink #2 6” underground and rink grid piping 100 PSI test pass, ready for pour.

Mechanical Rough-in Inspection Partial Pass 6/26/2025 (8:00 - 10:00) 6/26/2025 (AM) 06/26/2025
.3 for subfloor and snow melt
Corrections:


Miscellaneous/Other
Carried Forward
06/26/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
06/26/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Carried Forward
06/26/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Miscellaneous/Other
Carried Forward
06/26/2025
5/10- Rink #1 3” piping, headers and tubing. 100 psi hydrostatic test pass.

Miscellaneous/Other
Carried Forward
06/26/2025
6/11- Rink 2 melt grid and mains test pass

Miscellaneous/Other
Carried Forward
06/26/2025
6/20- Rink #2 6” underground and rink grid piping 100 PSI test pass, ready for pour.

Miscellaneous/Other
Carried Forward
06/26/2025
6/26-4-3” mains from chiller room to Rink 3. 100 psi air test pass

Mechanical Rough-in Inspection Partial Pass 6/27/2025 (10:00 - 12:00) 6/27/2025 (AM) 06/27/2025
Corrections:


Miscellaneous/Other
Carried Forward
06/27/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Carried Forward
06/27/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Carried Forward
06/27/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Miscellaneous/Other
Carried Forward
06/27/2025
5/10- Rink #1 3” piping, headers and tubing. 100 psi hydrostatic test pass.

Miscellaneous/Other
Carried Forward
06/27/2025
6/11- Rink 2 melt grid and mains test pass

Miscellaneous/Other
Carried Forward
06/27/2025
6/20- Rink #2 6” underground and rink grid piping 100 PSI test pass, ready for pour.

Miscellaneous/Other
Carried Forward
06/27/2025
6/26-4-3” mains from chiller room to Rink 3. 100 psi air test pass

Miscellaneous/Other
Carried Forward
06/27/2025
6/27- 6” underground mains from mechanical room to Rink-3. 100 psi test pass.

Mechanical Rough-in Inspection Passed 8/14/2025 (8:00 - 10:00) 8/14/2025 (AM) 08/14/2025
Corrections:


Miscellaneous/Other
Resolved
08/14/2025
4/25- 100 PSI air test on underground piping from equipment room. Will inspect insulation Monday morning.

Miscellaneous/Other
Resolved
08/14/2025
6/6- 100 PSI test on main underground fusion pipe from equipment room room to Rink #1 header location-Pass test

Miscellaneous/Other
Resolved
08/14/2025
5/14 100 PSI hydrostatic test on underground piping from Rink 2 mechanical room to ice sheet header location PASS

Miscellaneous/Other
Resolved
08/14/2025
5/10- Rink #1 3” piping, headers and tubing. 100 psi hydrostatic test pass.

Miscellaneous/Other
Resolved
08/14/2025
6/11- Rink 2 melt grid and mains test pass

Miscellaneous/Other
Resolved
08/14/2025
6/20- Rink #2 6” underground and rink grid piping 100 PSI test pass, ready for pour.

Miscellaneous/Other
Resolved
08/14/2025
6/26-4-3” mains from chiller room to Rink 3. 100 psi air test pass

Miscellaneous/Other
Resolved
08/14/2025
6/27- 6” underground mains from mechanical room to Rink-3. 100 psi test pass.

Miscellaneous/Other
Comment Only
08/14/2025
In floor piping for old labled rink #3 now labled as new rink #1. All tie-in's, piping for headers and rink, 100 lbs psi holding for all piping... approved

Mechanical Rough-in Inspection Passed 8/19/2025 (10:00 - 12:00) 8/19/2025 (AM) 08/19/2025
Corrections:


Miscellaneous/Other
Comment Only
08/19/2025
Pressure test holding at 100psi for... Rink 1, snow melt mains, subfloor mains and rink mains for piping up to south flex connections.

Mechanical Final Inspection Passed 8/25/2025 (8:00 - 10:00) 8/25/2025 (AM) 08/25/2025
Corrections:


Miscellaneous/Other
Resolved
08/25/2025
Ice Rink 1 air test on all piping, header and grid pass. Concrete pour on Tuesday

Miscellaneous/Other
Comment Only
08/25/2025
Rink 3 top cooling mat , piping as per design and air test holding at 100psi.... approved

Mechanical Final Inspection Not Ready 9/8/2025 (12:30 - 2:30) 9/8/2025 (PM) 09/08/2025
Corrections:


Miscellaneous/Other
Comment Only
09/08/2025
See progress inspection dated 9/8, not ready for final inspection at this time.

Progress Inspection Passed 11/4/2025 (8:00 - 10:00) 11/4/2025 (AM) 11/04/2025
Glycol piping
Corrections:


Miscellaneous/Other
Resolved
11/04/2025
Rink 3 snow melt piping and air test holding at 100 psi.. . approved

Miscellaneous/Other
Comment Only
11/04/2025
Air test on all chiller piping to roof and in chiller room holding at 100psi... approved

Mechanical Final Inspection Passed 1/14/2026 (Afternoon) 1/14/2026 (PM) 01/14/2026
Corrections:


Miscellaneous/Other
Comment Only
01/14/2026
Ammonia monitoring system has been tested, system is functioning as per the system design. All system alarms, shutdowns, exhaust fans, and sensors have been tested and are fully functioning. Final for this permit approved.