| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Mechanical Final Inspection | Pending | |||
| Mechanical Rough-in Inspection | Pending | |||
| Mechanical Rough-in Inspection | Partial Pass | 6/24/2025 (10:00 - 12:00) | 6/24/2025 (AM) | 06/24/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
06/24/2025
6/24- ductwork installed, approved for external insulation.
|
||||
| Progress Inspection | Passed | 8/19/2025 | 08/19/2025 | |
|
Corrections:
Miscellaneous/Other
Comment Only
08/19/2025
Viewed ductwork in penthouses, install and supports.... approved
|
||||
| Mechanical Rough-in Inspection | Partial Pass | 7/10/2025 (12:30 - 2:30) | 7/10/2025 (PM) | 08/19/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
08/19/2025
6/24- ductwork installed, approved for external insulation.
|
||||
| Mechanical Final Inspection | Passed | 8/29/2025 (8:00 - 10:00) | 8/29/2025 (AM) | 08/29/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/29/2025
See photo of map with the areas divided up in different phases. Phase 1A is completed including area F and part of E.
|
||||
| Mechanical Rough-in Inspection | Passed | 9/10/2025 (12:30 - 2:30) | 9/10/2025 (PM) | 09/10/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
09/10/2025
Main floor area A.... VAV and ductwork rough in and sealing ... approved.
Ok to insulate.
|
||||
| Mechanical Rough-in Inspection | Passed | 9/29/2025 (8:00 - 10:00) | 9/29/2025 (AM) | 09/29/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
09/29/2025
Arear A main floor rough-in completed, and final with all diffusers and eggcrates installed... approved
|
||||
| Mechanical Rough-in Inspection | Passed | 10/29/2025 (8:00 - 10:00) | 10/29/2025 (AM) | 10/29/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/29/2025
Area A, main floor... Viewed main trunkline in corridor and 2 duct runs to rooms.... ok to insulate.
|
||||
| Mechanical Rough-in Inspection | Partial Pass | 11/10/2025 (12:30 - 2:30) | 11/10/2025 (PM) | 11/10/2025 |
| Above Ceiling Inspection | Passed | 12/2/2025 (2:30 - 3:30) | 12/2/2025 (PM) | 12/02/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
12/02/2025
First floor, area A... diffusers and transfer ducts installed and approved for final of this area.
|
||||
| Mechanical Rough-in Inspection | Passed | 1/22/2026 (12:30 - 2:30) | 1/22/2026 (PM) | 01/22/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
01/22/2026
Continuing into next building phase.... VAV's and ducting install at rooms and corridor... approved and ok to wrap.
|
||||
| Mechanical Rough-in Inspection | Passed | 2/2/2026 (8:00 - 10:00) | 2/2/2026 (AM) | 02/02/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/02/2026
Main trunkline in corridor, approved and ok to wrap.
|
||||
| Mechanical Rough-in Inspection | Passed | 2/25/2026 (10:00 - 12:00) | 2/25/2026 (AM) | 02/25/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/25/2026
All mechanical on Main level B wing complete and approved for final.
|
||||
| Mechanical Rough-in Inspection | Passed | 4/8/2026 (10:00 - 12:00) | 4/8/2026 (AM) | 04/08/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
04/08/2026
Duct mains and branches to rooms of B wing lower level... approved.
80 psi air test on mains and branch piping of fin tube sustem in B wing lower level... approved
|
||||