Permit Application Status

PRMH202501278


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRMH202501278
Mechanical/HVAC
Permit(s) Issued
BLMGTN SCHOOL DIST #271
Alteration/Repair/Replace
Mechanical Improvements per documents by Wold Architects & Engineers. Mechanical air side of scope
02/06/2025
05/22/2025
03/28/2026

Locations

Permits

Permit Number: PRMH202501278

Mechanical
Issued
05/22/2025
03/28/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Final Inspection Pending
Mechanical Rough-in Inspection Partial Pass 6/24/2025 (10:00 - 12:00) 6/24/2025 (AM) 06/24/2025
Corrections:


Miscellaneous/Other
Carried Forward
06/24/2025
6/24- ductwork installed, approved for external insulation.

Progress Inspection Passed 8/19/2025 08/19/2025
Corrections:


Miscellaneous/Other
Comment Only
08/19/2025
Viewed ductwork in penthouses, install and supports.... approved

Mechanical Rough-in Inspection Partial Pass 7/10/2025 (12:30 - 2:30) 7/10/2025 (PM) 08/19/2025
Corrections:


Miscellaneous/Other
Carried Forward
08/19/2025
6/24- ductwork installed, approved for external insulation.

Mechanical Final Inspection Passed 8/29/2025 (8:00 - 10:00) 8/29/2025 (AM) 08/29/2025
Corrections:


Miscellaneous/Other
Comment Only
08/29/2025
See photo of map with the areas divided up in different phases. Phase 1A is completed including area F and part of E.

Mechanical Rough-in Inspection Passed 9/10/2025 (12:30 - 2:30) 9/10/2025 (PM) 09/10/2025
Corrections:


Miscellaneous/Other
Comment Only
09/10/2025
Main floor area A.... VAV and ductwork rough in and sealing ... approved. Ok to insulate.

Mechanical Rough-in Inspection Passed 9/29/2025 (8:00 - 10:00) 9/29/2025 (AM) 09/29/2025
Corrections:


Miscellaneous/Other
Comment Only
09/29/2025
Arear A main floor rough-in completed, and final with all diffusers and eggcrates installed... approved