PRMH202501278
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Mechanical Final Inspection | Pending | |||
Mechanical Rough-in Inspection | Partial Pass | 6/24/2025 (10:00 - 12:00) | 6/24/2025 (AM) | 06/24/2025 |
Corrections:
Miscellaneous/Other
Carried Forward
06/24/2025
6/24- ductwork installed, approved for external insulation.
|
||||
Progress Inspection | Passed | 8/19/2025 | 08/19/2025 | |
Corrections:
Miscellaneous/Other
Comment Only
08/19/2025
Viewed ductwork in penthouses, install and supports.... approved
|
||||
Mechanical Rough-in Inspection | Partial Pass | 7/10/2025 (12:30 - 2:30) | 7/10/2025 (PM) | 08/19/2025 |
Corrections:
Miscellaneous/Other
Carried Forward
08/19/2025
6/24- ductwork installed, approved for external insulation.
|
||||
Mechanical Final Inspection | Passed | 8/29/2025 (8:00 - 10:00) | 8/29/2025 (AM) | 08/29/2025 |
Corrections:
Miscellaneous/Other
Comment Only
08/29/2025
See photo of map with the areas divided up in different phases. Phase 1A is completed including area F and part of E.
|
||||
Mechanical Rough-in Inspection | Passed | 9/10/2025 (12:30 - 2:30) | 9/10/2025 (PM) | 09/10/2025 |
Corrections:
Miscellaneous/Other
Comment Only
09/10/2025
Main floor area A.... VAV and ductwork rough in and sealing ... approved.
Ok to insulate.
|
||||
Mechanical Rough-in Inspection | Passed | 9/29/2025 (8:00 - 10:00) | 9/29/2025 (AM) | 09/29/2025 |
Corrections:
Miscellaneous/Other
Comment Only
09/29/2025
Arear A main floor rough-in completed, and final with all diffusers and eggcrates installed... approved
|