PRMH202501449
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Mechanical Rough-in Inspection | Passed | 8/12/2025 (7:00 - 8:00) | 8/12/2025 (AM) | 08/12/2025 |
Corrections:
Miscellaneous/Other
Comment Only
08/12/2025
Grease duct and hood install... approved.
An outside extension will be installed at the termination to maintain the 10 ft distance from the intake air to the unit adjacent to the grease duct termination.
|
||||
Mechanical Final Inspection | Passed | 8/14/2025 (12:30 - 2:30) | 8/14/2025 (PM) | 08/14/2025 |
Corrections:
Miscellaneous/Other
Comment Only
08/14/2025
Hood, grease duct, insulation, and smoke testing to hood, along with extension added to the fan termination at roof to maintain the 10ft clearance to the intake air unit... approved.
Final for this permit approved.
|