Mechanical/HVAC
Finaled
G&I VIII WF PLAZA LLC
Alteration/Repair/Replace
HVAC PER PLANS
07/31/2025
08/11/2025
06/27/2026

Locations

Permits

Permit Number: PRMH202509300

Mechanical
Finaled
08/11/2025
06/27/2026

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Mechanical Rough-in Inspection Not Ready 9/16/2025 (12:30 - 2:30) 9/16/2025 (PM) 09/16/2025
9/16/2025 Contractor called to cancel inspection for today. Notified inspector [jsmidt @ 09/16/2025 9:51 AM]
Mechanical Rough-in Inspection Passed 9/25/2025 (10:00 - 12:00) 9/25/2025 (AM) 09/25/2025
Corrections:


Miscellaneous/Other
Comment Only
09/25/2025
Rough in inspection in area’s a and b okay.

Mechanical Rough-in Inspection Partial Pass 11/17/2025 (8:00 - 10:00) 11/17/2025 (AM) 11/17/2025
Corrections:


Miscellaneous/Other
Comment Only
11/17/2025
Above ceiling inspection okay. Schedule inspection for gas lines when ready.

Mechanical Rough-in Inspection Partial Pass 11/19/2025
Corrections:


Miscellaneous/Other
Comment Only
11/19/2025
Air test and Inspection of 1” gas line serving fireplaces okay. Schedule inspection of the other gas line serviing the other outdoor fire pit and indoor fireplace when ready.

Mechanical Rough-in Inspection Partial Pass 11/21/2025 (8:00 - 10:00) 11/21/2025 (AM) 11/21/2025
Corrections:


Miscellaneous/Other
Comment Only
11/21/2025
Inspection and air test for underground remaining gas line serving outdoor fire pits okay. Schedule when ready for air test or remainder of main.

Mechanical Final Inspection Passed 12/29/2025
Corrections:


Miscellaneous/Other
Comment Only
12/29/2025
Visual inspection and air test of interior gas new gas piping okay. Balance report has been received and reviewed.