Summary

PRPK202303832
Parking Lot
Finaled
WAL-MART RE BUSINESS TRUST
Alteration/Repair/Replace
Not Required
Scope of work is included in attached plans and includes the following services Removal and replacement of Concrete Milling and patching of parking lot Milling and repaving of parking lot Restriping of parking lot sign replacement
04/19/2023
05/19/2023
02/11/2024
08/15/2023

Locations

Permits

Permit Number: PRPK202303832

Parking Lot
Finaled
05/19/2023
02/11/2024

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Building Final Inspection Failed 6/22/2023 (12:30 - 2:30) 6/22/2023 (PM) 06/26/2023
Corrections:


Miscellaneous/Other
Carried Forward
06/26/2023
Accessible parking does not comply with Mn. 2020 accessibility code. 1) signage to stalles is to high. Signs to be 60"-66" max from grade to bottom of signs. 2) blue striping is not allowed for the accessible spaces. 3) van accessible spaces are not compliant, see Mn 2020 accessibility code section 503.3. The loading space must be adjacent to the parking stall. Refer to the Mn.2020 Accessibility Code sections 502 & 503 for requirements.

Building Final Inspection Failed 07/20/2023
Corrections:


Miscellaneous/Other
Carried Forward
07/20/2023
Accessible parking does not comply with Mn. 2020 accessibility code. 1) signage to stalles is to high. Signs to be 60"-66" max from grade to bottom of signs. 2) blue striping is not allowed for the accessible spaces. 3) van accessible spaces are not compliant, see Mn 2020 accessibility code section 503.3. The loading space must be adjacent to the parking stall. Refer to the Mn.2020 Accessibility Code sections 502 & 503 for requirements.

Miscellaneous/Other
Carried Forward
07/20/2023
Contractor came back to correct the accessibility issues from the previous inspection. The sign heights are corrected. Contractor put in a total of 5 van accessible stalls, of which two have the correct 8ft unloading zone. The three others have a 5ft access aisle, these are incorrect. Corrections needed... 1)install a total of 3 van accessible stalls with 8 ft access aisles on the passenger side. 2) stalls that are not van compliant need to have the van signage at the pavement blacked out and the van signage at the posts removed with the accessible signage of the stall lowered to 60"-66" from bottom of sign to pavements. Call for inspection when completed.

Building Final Inspection Passed 08/15/2023
Corrections:


Miscellaneous/Other
Resolved
08/15/2023
Accessible parking does not comply with Mn. 2020 accessibility code. 1) signage to stalles is to high. Signs to be 60"-66" max from grade to bottom of signs. 2) blue striping is not allowed for the accessible spaces. 3) van accessible spaces are not compliant, see Mn 2020 accessibility code section 503.3. The loading space must be adjacent to the parking stall. Refer to the Mn.2020 Accessibility Code sections 502 & 503 for requirements.

Miscellaneous/Other
Resolved
08/15/2023
Contractor came back to correct the accessibility issues from the previous inspection. The sign heights are corrected. Contractor put in a total of 5 van accessible stalls, of which two have the correct 8ft unloading zone. The three others have a 5ft access aisle, these are incorrect. Corrections needed... 1)install a total of 3 van accessible stalls with 8 ft access aisles on the passenger side. 2) stalls that are not van compliant need to have the van signage at the pavement blacked out and the van signage at the posts removed with the accessible signage of the stall lowered to 60"-66" from bottom of sign to pavements. Call for inspection when completed.

Miscellaneous/Other
Comment Only
08/15/2023
All signs and stalls for use with accessible parking have been corrected to meet code requirements. Final approved