Permit Application Status

PRPL201710741


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRPL201710741
Plumbing
Finaled
FELCOR/CSS HOLDINGS SPE
Alteration/Remodel
Remodel of existing mens and womens restrooms in Atrium. Remodel of existing mens and womens pool area restrooms. Remodel of existing cook to order kitchen in Atrium. Gas hook up for 2 griddles and one stove to existing gas line/cook line.
11/07/2017
05/10/2018
02/04/2019
08/08/2018

Locations

Permits

Permit Number: PRPL201710741

Plumbing
Finaled
05/10/2018
02/04/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Plumbing Rough-in Inspection Partial Pass 1/10/2018 (8:00 - 10:00) 1/10/2018 01/10/2018
Plumbing Rough-in Inspection Partial Pass 1/16/2018 (10:00 - 12:00) 1/16/2018 01/16/2018
Plumbing Rough-in Inspection Partial Pass 1/18/2018 (10:00 - 12:00) 1/18/2018 01/18/2018
Plumbing Rough-in Inspection Partial Pass 2/14/2018 (10:00 - 12:00) 2/14/2018 02/14/2018
Corrections:


Miscellaneous/Other
Comment Only
02/14/2018
Airtest on waste and vent for bathrooms. Water in progress, will schedule another inspection.

Plumbing Final Inspection Partial Pass 4/26/2018 (2:30 - 3:30) 4/26/2018 05/10/2018
Final was for bathrooms only-cook to order kitchen work ongoing-
Corrections:


Miscellaneous/Other
Comment Only
04/26/2018
Manometer test on bathrooms. Visual on lavs. Future walk through with water turned on.

Plumbing Rough-in Inspection Partial Pass 3/15/2018 (8:00 - 10:00) 3/15/2018 05/10/2018
Corrections:


Miscellaneous/Other
Comment Only
03/15/2018
Vents approved.

Plumbing Rough-in Inspection Partial Pass 3/21/2018 (2:30 - 3:30) 3/21/2018 05/10/2018
Corrections:


Miscellaneous/Other
Comment Only
03/21/2018
Airtest on grease waste line from one floor drain to 3 feet outside exterior wall.

Plumbing Rough-in Inspection Passed 5/10/2018 (8:00 - 3:30) 5/10/2018 05/10/2018
Corrections:


Miscellaneous/Other
Comment Only
05/10/2018
Airtest on waste and vent for kitchen.

Plumbing Rough-in Inspection Passed 5/14/2018 (8:00 - 10:00) 5/14/2018 05/14/2018
Corrections:


Miscellaneous/Other
Comment Only
05/14/2018
Gas line airtest ok. In future use 50 P.S.I. Gauge with air in midrange of dial for gaskins airtest. Refer to Mn Mechanical Code. Water line airtest ok. Add faucet for soap dispenser at 3 comp sink.

Plumbing Rough-in Inspection Passed 7/3/2018 (8:00 - 10:00) 7/3/2018 07/03/2018
Plumbing Final Inspection Passed 8/8/2018 (2:30 - 3:30) 8/8/2018 08/08/2018
Corrections:


All corrections have been made.
Resolved
08/08/2018
All corrections have been made. P.s. caulk hand sinks.