Permit Application Status

PRPL202112732


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PRPL202112732
Plumbing
Finaled
1701 AMERICAN BLVD LLC
Alteration/Repair/Replace
Inside Building Plumbing - Grease interceptor will be on separate permit.
09/24/2021
10/27/2021
04/25/2023
10/27/2022

Locations

Permits

Permit Number: PRPL202112732

Plumbing
Finaled
10/27/2021
04/25/2023

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Plumbing Rough-in Inspection Failed 12/10/2021 (10:00 - 12:00) 12/10/2021 (AM) 12/10/2021
Corrections:


Miscellaneous/Other
Comment Only
12/10/2021
Under ground never seen. Plumber said he was told pictures would be ok. Pictures or a camera scope will not suffice. Break up concrete, expose offsets, show location of clean outs, show 2 separate waste lines hang venting per plumbing code, provide air tests on sanitary and grease waste under ground. Air test on the entire waste and vent did not hold. Call for re-inspection.

Plumbing Rough-in Inspection Passed 11/5/2021 (10:00 - 12:00) 11/5/2021 (AM) 12/14/2021
Corrections:


Miscellaneous/Other
Comment Only
11/05/2021
under ground air test on grease waste Ok to backfill Future air test on sanitary line. Call for re-inspection 12/14 air on all ok to cover. Found leak

Plumbing Rough-in Inspection Passed 12/14/2021 (10:00 - 12:00) 12/14/2021 (AM) 12/14/2021
Plumbing Rough-in Inspection Passed 1/14/2022 (2:30 - 3:30) 1/14/2022 (PM) 01/14/2022
Visually inspected added rough in for lav sinks and 5 lb. air test
Plumbing Rough-in Inspection Passed 2/9/2022 (8:00 - 10:00) 2/9/2022 (PM) 02/10/2022
5 lb. Air test good on underground and above ground., and visual on added floor drains.
Plumbing Final Inspection Partial Pass 7/27/2022 (2:30 - 3:30) 7/27/2022 (PM) 07/27/2022
Corrections:


Miscellaneous/Other
Carried Forward
07/27/2022
Manometer test on new mens/womens bathroom group okay. Faucets in same bathrooms do not have an approved 1070 temperature limiting device installed. Self hygiene sprayers next to toilets do not have ASME A112.4.2/CSA B45.16 stamp or documentation showing standard. Water heater in kitchen needs to be on stand, or in a non metallic containment device.

Plumbing Final Inspection Not Ready 08/01/2022
Corrections:


Miscellaneous/Other
Comment Only
07/19/2022
Asked contractor to provide information about the water heater supplying the tempered water to the public lava in restrooms. There is an ASSE 1017 device installed at water heater, but does not meet the the requirement for public lav. Water heater needs to meet ASSE 1084.

Plumbing Final Inspection Not Ready 8/12/2022 (2:30 - 3:30) 8/12/2022 (PM) 08/12/2022
Cancelled by contractor for 8/1/2022 - jms 8/1/2022
Corrections:


Miscellaneous/Other
Carried Forward
08/12/2022
Manometer test on new mens/womens bathroom group okay. Faucets in same bathrooms do not have an approved 1070 temperature limiting device installed. Self hygiene sprayers next to toilets do not have ASME A112.4.2/CSA B45.16 stamp or documentation showing standard. Water heater in kitchen needs to be on stand, or in a non metallic containment device.

Plumbing Final Inspection Partial Pass 8/17/2022 (2:30 - 3:30) 8/17/2022 (PM) 08/17/2022
Corrections:


Miscellaneous/Other
Outstanding
08/17/2022
Manometer test okay on remaining waste and vent piping. Requiring an RPZ on water pipe feeding back to back bathrooms with personal hygiene hand sprayers. Water heater in kitchen area to be elevated 6” or placed in non metallic containment per EH. Finish insulating hot water piping.

Plumbing Final Inspection Passed w/ Conditions 10/27/2022 (10:00 - 12:00) 10/27/2022 (AM) 10/27/2022
Corrections:


Miscellaneous/Other
Resolved
10/27/2022
Manometer test on new mens/womens bathroom group okay. Faucets in same bathrooms do not have an approved 1070 temperature limiting device installed. Self hygiene sprayers next to toilets do not have ASME A112.4.2/CSA B45.16 stamp or documentation showing standard. Water heater in kitchen needs to be on stand, or in a non metallic containment device.

Miscellaneous/Other
Comment Only
10/27/2022
Corrections made. Hot water lines not insulted. Insulate in the ceiling as well as in mechanical rooms. Passed with condition to insulate the hot water lines. Pass will be revoked if condition is not met. Send photos to Dave Spaeth at 612-456-9633. Dave will make a final visit to see insulation in ceiling. He will make final determination when the insulation has been inspected.