PRPL202205949
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Plumbing Final Inspection | Pending | |||
Corrections:
Miscellaneous/Other
Outstanding
11/16/2022
RPZ from other permit not tested and tagged. Finish caulking fixtures, and install proper backflow on cooking appliance in question. Manometer test okay.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 7/11/2022 | 7/11/2022 (AM) | 07/11/2022 |
Corrections:
Miscellaneous/Other
Comment Only
07/11/2022
Visual on in wall dwv and gas. Air tests okay on waste and vent and in wall gas piping. Still need air test on gas main piping when complete and visual on horizontal dwv below floor.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 7/27/2022 (12:30 - 2:30) | 7/27/2022 (PM) | 07/27/2022 |
Corrections:
Miscellaneous/Other
Comment Only
07/27/2022
Visual on horizontal piping below floor. Still need air test low pressure gas main piping.
|
||||
Plumbing Rough-in Inspection | Passed | 8/5/2022 (8:00 - 10:00) | 8/5/2022 (AM) | 08/05/2022 |
Plumbing Final Inspection | Partial Pass | 11/1/2022 (2:30 - 3:30) | 11/1/2022 (PM) | 11/01/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
11/01/2022
RPZ from other permit not tested and tagged. Finish caulking fixtures, and install proper backflow on cooking appliance in question. Manometer test okay.
|
||||
Plumbing Final Inspection | Partial Pass | 11/16/2022 (10:00 - 12:00) | 11/16/2022 (AM) | 11/16/2022 |
Corrections:
Miscellaneous/Other
Carried Forward
11/16/2022
RPZ from other permit not tested and tagged. Finish caulking fixtures, and install proper backflow on cooking appliance in question. Manometer test okay.
|
||||
Miscellaneous/Other
Comment Only
11/16/2022
Partial pass.
Bidet to be installed
|