PRPL202408527
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Plumbing Rough-in Inspection | Partial Pass | 7/29/2024 (2:30 - 3:30) | 7/29/2024 (PM) | 07/29/2024 |
Corrections:
Miscellaneous/Other
Comment Only
07/29/2024
Beginning of underground typing looks good.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 7/30/2024 (12:30 - 2:30) | 7/30/2024 (PM) | 07/30/2024 |
Corrections:
Miscellaneous/Other
Comment Only
07/30/2024
Underground piping for sanitary and flamable waste look good with 5 pound air test.
|
||||
Progress Inspection | Partial Pass | 9/16/2024 (8:00 - 10:00) | 9/16/2024 (AM) | 09/16/2024 |
Plumbing Rough-in Inspection | Partial Pass | 9/19/2024 (8:00 - 10:00) | 9/19/2024 (AM) | 09/19/2024 |
Corrections:
Miscellaneous/Other
Comment Only
09/19/2024
Visual on waste and vent first floor unit 111 to Eastside looks good. Plumber to do long sweeps on dirty arms. Unit 125 has that correction.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 10/3/2024 (10:00 - 12:00) | 10/3/2024 (AM) | 10/03/2024 |
Corrections:
Miscellaneous/Other
Comment Only
10/03/2024
Five pound air test on stacks 23 through 29 look good.
Visual on fourth floor piping looks good.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 10/8/2024 (2:30 - 3:30) | 10/8/2024 (PM) | 10/08/2024 |
Corrections:
Miscellaneous/Other
Comment Only
10/08/2024
Visual for in wall piping on third floor complete.
|
||||
Progress Inspection | Partial Pass | 10/9/2024 (12:30 - 2:30) | 10/9/2024 (PM) | 10/09/2024 |
Air Test inspection | ||||
Corrections:
Miscellaneous/Other
Comment Only
10/09/2024
Air test on floors, one through four on waste event all good. Call for inspection for tub installation to see traps and valves.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 10/15/2024 (10:00 - 12:00) | 10/15/2024 (AM) | 10/15/2024 |
Air test for roof drains and visual for traps for the showers | ||||
Corrections:
Miscellaneous/Other
Resolved
10/15/2024
|
||||
Progress Inspection | Partial Pass | 10/28/2024 (8:00 - 10:00) | 10/28/2024 (AM) | 10/28/2024 |
Traps on the showers | ||||
Corrections:
Miscellaneous/Other
Comment Only
10/28/2024
Air test on all overflows looks good.
|
||||
Plumbing Rough-in Inspection | Partial Pass | 12/4/2024 (10:00 - 12:00) | 12/4/2024 (AM) | 12/04/2024 |
Air Test | ||||
Corrections:
Miscellaneous/Other
Comment Only
12/04/2024
Five pound air test and visual on piping in parking garage looks good.
|
||||
Plumbing Final Inspection | Partial Pass | 03/04/2025 | ||
Corrections:
Miscellaneous/Other
Comment Only
03/04/2025
Manometer test on entire building is OK. Fourth floor visual checks out as well.
|
||||
Progress Inspection | Partial Pass | 3/4/2025 (8:00 - 10:00) | 3/4/2025 (AM) | 03/04/2025 |
Corrections:
Miscellaneous/Other
Comment Only
03/04/2025
Final visual on third floor fixtures, all sealed.
|
||||
Plumbing Final Inspection | Partial Pass | 3/6/2025 (10:00 - 12:00) | 3/6/2025 (AM) | 03/06/2025 |
Corrections:
Miscellaneous/Other
Comment Only
03/06/2025
Check caulking on three units on second floor in the tubs. Need faucet on first floor hall bath. Need test and certification on RPZ for lawn irrigation.
|
||||
Plumbing Final Inspection | Partial Pass | 3/10/2025 (8:00 - 10:00) | 3/10/2025 (AM) | 03/10/2025 |
Corrections:
Miscellaneous/Other
Comment Only
03/10/2025
All units look good. Inspections needed on RPZ‘s once they are tested and test report is in the city.
|
||||
Plumbing Final Inspection | Passed | 3/11/2025 (8:00 - 10:00) | 3/11/2025 (AM) | 03/11/2025 |
Corrections:
Miscellaneous/Other
Comment Only
03/11/2025
RPZ‘s for lawn, irrigation and trash wash down are tested and tagged.
|
||||
Plumbing Rough-in Inspection | Passed | 03/19/2025 |