PRPL202413101
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Plumbing Rough-in Inspection | Partial Pass | 1/8/2025 (10:00 - 12:00) | 1/8/2025 (AM) | 01/08/2025 |
| underground | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
01/08/2025
Flammable waste and sanitary underground on east side with 5 pound air test looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 1/9/2025 (8:00 - 10:00) | 1/9/2025 (AM) | 01/09/2025 |
| underground | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
01/09/2025
Installation of storm on east side underground looks good with air test.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 1/13/2025 (2:30 - 3:30) | 1/13/2025 (PM) | 01/13/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
01/13/2025
Rest of underground piping complete on west side. Want to see air test on broken 6 inch pipe.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 1/14/2025 (8:00 - 10:00) | 1/14/2025 (AM) | 01/14/2025 |
| Plumbing Rough-in Inspection | Partial Pass | 4/1/2025 (12:30 - 2:30) | 4/1/2025 (PM) | 04/01/2025 |
| Plumbing Rough-in Inspection | Partial Pass | 5/6/2025 (2:30 - 3:30) | 5/6/2025 (PM) | 05/06/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/06/2025
Air test for portion of unit stacks okay.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 5/7/2025 (10:00 - 12:00) | 5/7/2025 (AM) | 05/07/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/07/2025
Air test for portion of unit stacks looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 5/8/2025 (8:00 - 10:00) | 5/8/2025 (AM) | 05/08/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/08/2025
Air test for portion of unit stacks all looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 5/12/2025 (12:30 - 2:30) | 5/12/2025 (PM) | 05/12/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/12/2025
Air test for portion of unit stacks looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 5/13/2025 (10:00 - 12:00) | 5/13/2025 (AM) | 05/13/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/13/2025
Air tests for remaining unit piping okay. Air tests for a portion of storm piping above garage okay. Air test still need on remaining storm piping risers above garage.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 5/14/2025 (10:00 - 12:00) | 5/14/2025 (AM) | 05/14/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/14/2025
Air test at rest of rain leaders in parking garage looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 5/21/2025 (12:30 - 2:30) | 5/21/2025 (PM) | 05/21/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
05/21/2025
Visual on piping in wall on fifth floor southwest side to firewall.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 6/4/2025 (10:00 - 12:00) | 6/4/2025 (AM) | 06/04/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
06/04/2025
Fifth floor visual on plumbing is complete.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 6/18/2025 (10:00 - 12:00) | 6/18/2025 (AM) | 06/18/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
06/18/2025
Visuals on fourth floor east side and first floor unit 115 and 117 are OK.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 7/2/2025 (10:00 - 12:00) | 7/2/2025 (AM) | 07/02/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
07/02/2025
Visual on rough-in plumbing fourth floor West side looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 7/15/2025 (12:30 - 2:30) | 7/15/2025 (PM) | 07/15/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
07/15/2025
Visual on third floor east side of waste and vent looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 7/30/2025 (10:00 - 12:00) | 7/30/2025 (AM) | 07/30/2025 |
| 3rd floor inspection | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
07/30/2025
Visual on piping on third floor west side all looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 8/6/2025 (10:00 - 12:00) | 8/6/2025 (AM) | 08/06/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/06/2025
Rough-ins on second floor east side look good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 8/18/2025 (2:30 - 3:30) | 8/18/2025 (PM) | 08/19/2025 |
|
Corrections:
Miscellaneous/Other
Carried Forward
08/20/2025
Piping on second floor west side looks good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 8/25/2025 (8:00 - 10:00) | 8/25/2025 (AM) | 08/25/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/25/2025
Air test on garage plumbing West side is good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 8/25/2025 (12:30 - 2:30) | 8/25/2025 (PM) | 08/25/2025 |
|
Corrections:
Miscellaneous/Other
Resolved
08/25/2025
Piping on second floor west side looks good.
|
||||
|
Miscellaneous/Other
Comment Only
08/25/2025
Visual on plumbing first floor. B is good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 8/26/2025 (2:30 - 3:30) | 8/26/2025 (PM) | 08/26/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/26/2025
Air test on stacks north Northwest area B look good.
|
||||
| Plumbing Final Inspection | Partial Pass | 08/27/2025 | ||
|
Corrections:
Miscellaneous/Other
Comment Only
08/27/2025
Visual and plumbing in area a is good.
|
||||
| Plumbing Rough-in Inspection | Partial Pass | 8/27/2025 (3:30 - 4:00) | 8/27/2025 (PM) | 08/27/2025 |
|
Corrections:
Miscellaneous/Other
Comment Only
08/27/2025
Air test on rest of plumbing stacks of building look good.
|
||||
| Progress Inspection | Partial Pass | 2/3/2026 (10:00 - 12:00) | 2/3/2026 (AM) | 02/03/2026 |
| pneumometer Inspection | ||||
|
Corrections:
Miscellaneous/Other
Comment Only
02/03/2026
Manometer test on stacks 132 ,140,142 and 144 approved
|
||||
| Progress Inspection | Partial Pass | 2/4/2026 (10:00 - 12:00) | 2/4/2026 (AM) | 02/04/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/04/2026
Monometer good on stacks 148,150-149,147,143,141,139,128,138,136,126,131,129
|
||||
| Plumbing Final Inspection | Partial Pass | 2/10/2026 (12:30 - 2:30) | 2/10/2026 (PM) | 02/10/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/10/2026
Manometer on plumbing stacks, complete and approved.
|
||||
| Plumbing Final Inspection | Partial Pass | 2/18/2026 (10:00 - 12:00) | 2/18/2026 (AM) | 02/18/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/18/2026
Manometers don’t inflammable waste in basement parking garage approved. Fifth floor visuals on units on east side approved.
|
||||
| Plumbing Final Inspection | Partial Pass | 2/19/2026 (10:00 - 12:00) | 2/19/2026 (AM) | 02/19/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/19/2026
Visual on fifth floor units west side approved.
|
||||
| Plumbing Final Inspection | Partial Pass | 2/23/2026 (10:00 - 12:00) | 2/23/2026 (AM) | 02/23/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/23/2026
Forth floor east wing units approved.
|
||||
| Plumbing Final Inspection | Partial Pass | 2/20/2026 (10:00 - 12:00) | 2/20/2026 (AM) | 02/23/2026 |
| Plumbing Final Inspection | Partial Pass | 2/25/2026 | 2/25/2026 (PM) | 02/25/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/25/2026
Plumbing approved in units on 4th floor area A and 3rd floor area B.
|
||||
| Plumbing Final Inspection | Partial Pass | 2/26/2026 (12:30 - 2:30) | 2/26/2026 (PM) | 02/26/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
02/26/2026
Visuals on fixtures from third floor area A to second floor area B approved.
|
||||
| Plumbing Final Inspection | Partial Pass | 3/3/2026 (Afternoon) | 3/3/2026 (PM) | 03/03/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
03/03/2026
Visuals on 2B and 1A complete.
|
||||
| Plumbing Final Inspection | Partial Pass | 3/4/2026 (Morning) | 3/4/2026 (AM) | 03/04/2026 |
|
Corrections:
Miscellaneous/Other
Comment Only
03/04/2026
Visuals of plumbing fixtures and units complete and approved. Still waiting for inspection on RPZ’s once they have been tested and tagged.
|
||||
| Plumbing Final Inspection | VOID | 3/12/2026 (8:00 - 10:00) | 03/12/2026 | |
|
Corrections:
Miscellaneous/Other
Comment Only
05/08/2025
Air test for portion of unit stacks all looks good.
|
||||
| Plumbing Final Inspection | Passed | 3/12/2026 (8:00 - 10:00) | 03/12/2026 | |
|
Corrections:
Miscellaneous/Other
Comment Only
03/12/2026
RPZ‘s have been tested and put into service.
|
||||
| Plumbing Rough-in Inspection | Passed | 8/27/2025 (8:00 - 10:00) | 8/27/2025 (AM) | 03/12/2026 |